Three Core LS0H SWA Cable

Application
Three core LS0H (Low smoke zero halogen) steel wired armoured cable is designed for use where fire, smoke emission or toxic fumes would create a potential threat to life and equipment. It is suitable for use in mains supply electricity and is the accepted standard for underground, outdoors and indoors installation. Its steel wired armouring offers a high level of mechanical protection, making it ideal for direct burial.
Construction
Plain stranded copper conductor with a XLPE (Cross-Linked Polyethylene) insulation and a LS0H bedding.
Armouring is galvanised steel wired and the sheath is black LS0H.
Technical Data
Voltage: 600/1000V.
Temperature Range: -0 to +90°C.
Relevant Standards
BS5467, IEC60502
Drum Sizes
Cut to size.
Order Code | Cable Size | Approx Rating (amps) | Gland Pack | Cleat | Overall Dia (mm) |
---|---|---|---|---|---|
1.56943X | 1.5mm | 16 | BW20S | 6 | 12.6 |
2.56943X | 2.5mm | 20 | BW20S | 6 | 14.1 |
4.06943X | 4.0mm | 27 | BW20 | 7 | 15.3 |
6.06943X | 6.0mm | 34 | BW20 | 8 | 16.6 |
10.06943X | 10.0mm | 46 | BW25 | 9 | 19.5 |
16.06943X | 16.0mm | 62 | BW25 | 10 | 21.6 |
25.06943X | 25.0mm | 80 | BW32 | 11 | 25.5 |
Larger sizes (or larger core numbers, ie 5 or 7 core) of LS0H SWA cable are also normally available from stock. Please contact our sales team with your requirements.
All of the gland packs detailed in the above table are of standard 'BW' type. Please replace 'BW' with 'CW' for weatherproof gland packs or 'LSF' for low smoke and fume gland packs.
ie For 6.0mm 4C SWA outdoor use, select CW20 weatherproof gland pack.
Please note that SWA gland packs contain two complete glands up to size 32. Gland pack sizes of 40 and upwards contain one complete gland.