Double Insulated Mains Cable

Application
Double insulated mains cable is designed for connection of service heads and mains supplies. It is often referred to as 'metre tails'.
Construction
Plain annealed copper solid (1.0 - 2.5mm) or stranded (4.0 - 25mm) circular conductor to BS 6360, with a PVC insulation and a PVC sheath.
Core Colours:
Core colours: Available in brown and blue.
Technical Data
Voltage: 300/500V.
Temperature Range: -5 to +70°C.
Relevant Standards
To BS6004.
Drum Sizes
Cut to size.
Order Code | Description | Approx Rating (amps) | Overall Diameter (mm) | Stranding (mm) |
---|---|---|---|---|
1.06181Y | 1.0mm Double Insulated Mains Cable | 12 | 4.1 | N/A |
1.56181Y | 1.5mm Double Insulated Mains Cable | 16 | 4.5 | N/A |
2.56181Y | 2.5mm Double Insulated Mains Cable | 20 | 5.1 | N/A |
4.06181Y | 4.0mm Double Insulated Mains Cable | 27 | 6.1 | 7/1.25 |
6.06181Y | 6.0mm Double Insulated Mains Cable | 34 | 8.7 | 7/1.44 |
10.06181Y | 10.0mm Double Insulated Mains Cable | 46 | 9.0 | 7/1.44 |
16.06181Y | 16.0mm Double Insulated Mains Cable | 62 | 9.5 | 7/1.70 |
25.06181Y | 25.0mm Double Insulated Mains Cable | 80 | 11.2 | 7/1.14 |
35.06181Y | 35.0mm Double Insulated Mains Cable | 99 | 13.7 | 19/1.53 |
50.06181Y | 50.0mm Double Insulated Mains Cable | 118 | 15.2 | 19/1.78 |
Note: 6181Y cable is available in Grey/Brown and Grey/Blue. Please specify the colour you require.